Skip to main content
Home / Products / Boiler Water Treatment / BOILPLEX AT Hardness Control

BOILPLEX AT Hardness Control

Boiler Water Treatment
Product Code / SKU:  RXSOL-40-5027-025

In addition to controlling the alkali content, scale and sediment, Boilplex ATprotects the condensate system (Steam superheater) from corrosion caused by low pH. Boilplex AT control sludge and sediment deposition by adsorption on sludge boiler surfaces...

Prompt industrial dispatch Bulk & custom packaging (20L, 25L, 210L, IBC) Certificate of Analysis (COA) & MSDS available

Product Overview

BOILPLEX AT Hardness Control is specialized Boiler Water treatment product to KEEP Boiler water Clear and Clean SLUDGE FREE. Boilplex AT is basically phosphates combination with synthetic polymers.  Very easy to use, provides flexibility in system operation and control over the operation of the auxiliary and exhaust gas heaters on the boats.  The tool is designed to maintain the cleanliness of the boiler at unstable as feedwater.

Technical Specifications

Boilplex AT control sludge and sediment deposition by adsorption on sludge boiler surfaces;  particles are soft, do not stick together, smoothly removed by purging.  Boilplex AT contained component, iron oxide passivation and not giving cheance to spread throughout system. In addition to controlling the alkali content, scale and sediment, Boilplex AT protects the condensate system (Steam superheater) from corrosion caused by low pH.  In conjunction with Boilplex AT provides the most modern, safe and effective program to protect the boilers on ships.

Application & Dosage

Application Instructions


Recommended Dosage

 

Appearance

: Clear liquid

Specific gravity at 25 º C (77 º F)

: 1.056

Fire

: off

Freezing temperature

: -6.6 º C (20 º F)

pH

: 13.4

Stability after freeze / that

: yes

Available Packaging & Quantities

Regularly enter solutions drugs Boilplex AT with a dosing device BWT Dosing System in feedwater recirculation outlet below which returns cascading water in the tank.  If there is no recirculation of feedwater, the drug should be submitted in suction tube feeding pump.  When using gravity dispenser the drug should be fed to the point of feed water tank or in cascade.  Drug supply line should be higher than normal water level (about 1 meter) and as close as possible to the fence of water nutrient pump. Boilplex AT to be dissolved in distilled water or condensate in the dispensing tank and gradually continuously fed for 24 hours, keeping the system demand.  The daily dosage is depend on the volume of the system, the condensate quality and purity, as well as the quality and quantity of the feed water system.  For standard operating systems the dosage Boilplex AT is about 1 liter a day.

Very large systems or in non-standard conditions will have a greater need for preparation. Many factors can affect the initial dose of the drug.  The two most important factors - quality feedwater and the boiler. The recommended initial dose of 2.5 to 5 liters per tonne of water system.  After the initial filling of the product during operation of the system on a daily basis should perform a test to adjust the dosage.  Low quality feedwater demands increase quantities of preparation, as well as leaching of the polluted water from the boiler of the boiler due to the settling of particles on bottom of the boiler during system shutdown.  This in turn entails the need for additional purging and increase the amount of drug. 

The main objective of the program - to prevent fouling.  The most effective way to fight c deposits is to use distilled water feed.  Boilplex AT created for removing water hardness instability.

 Blowdown

Purge procedure is necessary for the effectiveness of any treatment program and boiler watershall be in accordance recommendations manufacturer's instructions.  Purging is required to remove the precipitate dissolved and suspended solids.  Normal regular purging with sufficient neutral of conductivity 700 μmho.  A higher rate of conductivity (above 700 μmho) frequency blowdown should be increased.  Additionally, it is recommended to wash weekly collector or separator pair (if any) to reduce the accumulation of sludge.

Handling, Storage & Safety

72-75

Phosphate and synthetic polymer Based Boiler water treatment chemicals to control sludge for low and medium pressure boilers  RXSOL BOILPLEX AT Hardness Control manufacturer ans supplier in Mumbai, Gandhidham Surat Gujrat, Chennai, Ennore, Visakhapatnam VIZAG Andhra Pradesh, Kolkata, Haldia, Paradip, Fujairah, Sharjah, Ajman, Abudhabi, Muscat Oman, Canada BE, Nairobi Mombasa, Kenya, Jinja Kampala, Uganda

Target Industries & Supply Locations

Useful Applications

BOILPLEX AT Hardness Control is specialized Boiler Water treatment product to KEEP Boiler water Clear and Clean SLUDGE FREE.
Boilplex AT is basically phosphates combination with synthetic polymers.  Very easy to use, provides flexibility in system operation and control over the operation of the auxiliary and exhaust gas heaters on the boats.  The tool is designed to maintain the cleanliness of the boiler at unstable as feedwater.

Supply & Distribution Locations

Phosphate and synthetic polymer Based Boiler water treatment chemicals to control sludge for low and medium pressure boilers which results in the clean boiler water. USES of RXSOL BOILPLEX AT Hardness Control provide tolerance of feedwater quality fluctuations. The ready stock of BOILPLEX AT Hardness Control is in 25, 50 Ltr packing.

Need pricing or a bulk quotation?

Tell us your required product and quantity — our technical sales team replies promptly with pricing and availability.

Request a Quote